Explosion Vented Equipment System Protection Guide. Robert C. Comer

Читать онлайн.
Название Explosion Vented Equipment System Protection Guide
Автор произведения Robert C. Comer
Жанр Химия
Серия
Издательство Химия
Год выпуска 0
isbn 9781119640073



Скачать книгу

gasses or shrapnel escaping from the equipment. If hot gasses or shrapnel escapes from the equipment any dust accumulated on the floor, beams, or other equipment in the area due to poor housekeeping would be blown into the air where it forms an explosive mixture that becomes a secondary explosion, usually of higher intensity than the first explosion. Extensive building and equipment damage and personnel injury or death would occur.

      The analysis in this manual is presented to allow a licensed or competent unlicensed engineer, that by education or experience understands the concepts presented in this book, to determine the required reinforcing design when reviewing the equipment supplied by the manufacturer.

      All he/she needs to know is the explosion vent size, the vented explosion flowing pressure, PRed, and the equipment wall material and thickness.

      An equipment manufacturer can also use this manual to design their equipment to sustain any pressure dictated by the user after a venting analysis is performed, an explosion relief element is decided on and PRed is determined.

      Dust collectors are either cylindrical or square/rectangular shaped. Cylindrical dust collectors are usually structurally sound except for those with a flat roof and an access door that may require reinforcing. Most dust collectors and associated equipment have large, flat, thin panel construction that is very easy to analyze for reinforcing. A weak link in both types of construction is the roof, access door, and door restraints (hinges and latches). In almost every case, the access door and its restraints must be reinforced so that it does not fail and allow hot gas or shrapnel to be discharged into the surrounding area where employees may be working, or other equipment may be damaged. A secondary greater explosion of dust on surfaces in the area by poor housekeeping could occur that could destroy the building structure. Flow activated explosion isolation valves and rotary valves installed in the equipment upstream and downstream of the dust collector contain the combustible dust deflagration products, smoke, dust, burning debris from traveling beyond the equipment.

      This section of the book is presented to allow a competent engineer that by education or experience understands the concepts presented in this book, to determine the explosion relief element to safely vent and lower the explosion flowing pressure, PRed, to a reasonable level so that reinforcing, if required, can be analyzed and designed in a practical, economical manner as defined in Part 1.

      Required for this section is the process dust explosion characteristics, Kst, Pmax, and the dust handling system geometry. If the dust explosion characteristics are not known, a sample of the dust must be tested to obtain these characteristics. The table of dust characteristic values presented in this book is for estimating purposes only. To ensure proper design, a tested sample of dust must be used.

      How to Use This Book

      There are two parts to this book. Part I provides the structural analysis and design for reinforcing of dust handling equipment and explosion relief ducting to prevent a catastrophic failure of the equipment during a dust explosion. Part II provides the analysis of dust handling equipment to determine the size of the explosion relief burst element and the explosion relief flowing pressure (PRed) based on the process dust explosion characteristics and geometry of the equipment.

      Existing in‐house dust collection systems or new proposed equipment: If the existing or new equipment has been certified by the manufacturer for the allowable safe operating positive pressure on the drawings or in the specifications, it must be determined from the manufacturer, the design criteria that was used (% of yield or ultimate stress). If 2/3 of the 0.2% yield strength was not used as the limiting stress, the equipment does not comply with NFPA 68 (2013) “Standards on Explosion Protection by Deflagration Venting.” Part 1 of this book will provide the guidance and structural analysis to ensure that the equipment complies.

      If the equipment has been designed to be explosion vented and has an explosion vent built‐in or proposed, there must have been an explosion venting analysis performed specific for the process dust being handled and geometry of the system. If an analysis is provided with the resultant explosion flowing pressure (PRed), then go to Part 1 directly to ensure the integrity of the system. If the manufacturer does not provide the analysis, Part 2 of this book will provide the guidance and analysis to size the explosion relief burst element, ducting and to calculate the explosion flowing pressure (PRed) before accessing Part 1 to ensure that the system is structurally sound and safely vented.

      Symbols